IEC 1000-3-3 : Flicker Simulation for an Industrial Blower
First Step:
Choose Options / Simulation / SIM to change to simulation mode
Second Step:
Enter the Power versus Time values into the table

Last Step :
Run the Flicker test as usual and you get the results like or a real measurement. Below you see the protocol as automatically generated in HTML mode.
Flicker Emission - IEC 1000-3-3 , EN 61000-3-3 , (EN60555-3)
Comply: IEC 61000-3-3 Ed.1.1 :2002 (incl. Amd.1) - IEC 61000-4-15 Ed.1.0 :1997 (incl. Amd.1)
EMC PARTNER AG , Laufen
HARCS Setup File :
Operator Reto Casanova Unit 2000VA Fan Serialnumber none Bemerkungen : operating for 15sec every 30sec
Full Bar : Actual Values
Empty Bar : Maximum Values
Circles : Average Values
Blue : Current , Green : Voltage , Red : Failed
Measurement
Date : 08.08.02 07:48:09 V3.10
Test - Time : 1 x 3min = 3min ( 100 %)
LIN (Line Impedance Network) : SLIN 0.24ohm +j0.15ohm N:0.16ohm +j0.10ohm
Limits : Plt : 0.60 Pst : 1.00
dmax : 4.00 % dc : 3.00 %
dtLim: 3.00 % dt>Lim: 200ms
Flicker Simulation
Plt = 1.879 FAILED
Pst P50s P10s P3s P1s P0.1s Fli(m)
1 1.879 0.010 0.102 3.975 22.65 65.37 65.60
Definitions of Abbreviations Plt Long term Flicker over all Pst cycles For every Pst-cycle: Pst Short term Flicker P50s Flicker level reached during 50% of the test time P10s Flicker level reached during 10% of the test time P3s Flicker level reached during 3% of the test time P1s Flicker level reached during 1% of the test time P0.1s Flicker level reached during 0.1% of the test time Fli(max) Maximum Flicker level during test time General : - The values marked with "***" are actual values which could vary during test-time and are taken at the time of protocol printout.
Notes Flicker Simulation of a 2000VA Fan ---------------------------------- The Fan is switched on for 15 seconds every 30 seconds. A high start-up current of more than 200% causes a high Flicker Level. - choose : Options / Simulation / SIM for the simulation mode. - Close the simulation window and run the test as in normal measuring mode. - You will get a Pst and Plt of around 1.90 To get a lower Flicker Level you can reduce the start-up current for example with an electronic softstart device. The example "Fan2.hrp" shows the same Fan with a softstart electronic.