Harmonic Immunity - IEC 1000-4-13
Comply: IEC 61000-4-13 Ed.1.0 :2002 - IEC 61000-4-7 Ed.1.0 :1991
EMC PARTNER AG, SWITZERLAND
HARCS Setup File :
Operator : R.Casanova Unit : Data-Recorder Serialnumber : unknown Bemerkungen : Unit has passed the immunity test
Measurement Date : 01.09.02 11:45:19 V3.10 Urms = 230.1V Freq = 50.000 Range: 1A Irms = 0.379A Ipk = 0.814A cf = 2.149 P = 66.4W Pap = 87.17VA pf = 0.762 THDi = 0.10 % THDu = 0.10 % Class 3 Harmonic Immunity - IEC 1000-4-13 Flat Curve 2 min passed Overswing 2 min passed Frequency Sweep 12 min failed Stepwise Individual 15 min passed Total: 31 min (max.) Test completed, Result: PASSED
Harmonic Immunity -- Test Procedure : Class A Flat Curve 2 min Amplitude of flat part = 80% Overswing 2 min 3rd Harmonic = 8.0% 5th Harmonic = 5.0% Frequency Sweep 12 min(total) 5.0 min from 15..100 Hz : Level = 4.5% 2.5 min from 100..500 Hz : Level = 14% 2.5 min from 500..1000 Hz : Level = 9.0% 2.0 min from 1000..2000 Hz : Level = 6.0% Stepwise Individual 15 min(total) ca. 2 min from 16..100 Hz every 5Hz for 5sec. 2.(100Hz) : Level = 5.0% 0° Level = 5.0% 180° Interharm. : Level = 4.0% ca. 4 min from 100..500 Hz every 10Hz for 5sec. 3.(150Hz) : Level = 9.0% 0° Level = 9.0% 180° 4.(200Hz) : Level = 2.0% 0° 5.(250Hz) : Level = 12% 0° Level = 12% 180° 6.(300Hz) : Level = 1.5% 0° 7.(350Hz) : Level = 10% 0° Level = 10% 180° 8.(400Hz) : Level = 1.5% 0° 9.(450Hz) : Level = 4.0% 0° Level = 4.0% 180° 10.(500Hz) : Level = 1.5% 0° Interharm. : Level = 9.0% ca. 5 min from 500..1000 Hz every 10Hz for 5sec. 11.(550Hz) : Level = 7.0% 0° 12.(600Hz) : Level = 1.5% 0° 13.(650Hz) : Level = 7.0% 0° 14.(700Hz) : Level = 1.5% 0° 15.(750Hz) : Level = 3.0% 0° 16.(800Hz) : Level = 1.5% 0° 17.(850Hz) : Level = 6.0% 0° 18.(900Hz) : Level = 1.5% 0° 19.(950Hz) : Level = 6.0% 0° 20.(1000Hz) : Level = 1.5% 0° Interharm. : Level = 5.0% over 750Hz : Level = 3.0% ca. 4 min from 1000..2000 Hz every 10Hz for 5sec. 21.(1050Hz) : Level = 2.0% 0° 22.(1100Hz) : Level = 1.5% 0° 23.(1150Hz) : Level = 6.0% 0° 24.(1200Hz) : Level = 1.5% 0° 25.(1250Hz) : Level = 6.0% 0° 26.(1300Hz) : Level = 1.5% 0° 27.(1350Hz) : Level = 2.0% 0° 28.(1400Hz) : Level = 1.5% 0° 29.(1450Hz) : Level = 5.0% 0° 30.(1500Hz) : Level = 1.5% 0° 31.(1550Hz) : Level = 3.0% 0° 32.(1600Hz) : Level = 1.5% 0° 33.(1650Hz) : Level = 2.0% 0° 34.(1700Hz) : Level = 1.5% 0° 35.(1750Hz) : Level = 3.0% 0° 36.(1800Hz) : Level = 1.5% 0° 37.(1850Hz) : Level = 3.0% 0° 38.(1900Hz) : Level = 1.5% 0° 39.(1950Hz) : Level = 2.0% 0° 40.(2000Hz) : Level = 1.5% 0° Interharm. : Level = 2.0%
Definitions of Abbreviations Urms *** Actual total Voltage in Volt RMS Irms *** Actual total Current in Ampere RMS Ipk *** Actual Peak value of the Current in Ampere cf *** Actual Crest Factor (Ipk/Irms) P *** Actual Active Power in Watt Pap *** Actual Apparent Power in VA (Urms*Irms) pf *** Actual Power Factor (P/Pap) THDi *** Actual Total Harmonic Current Distortion in % THDu *** Actual Total Harmonic Voltage Distortion in %
Notes
The Recorder was crashing at 1000Hz during the frequency sweep,
so the "individual harmonics" test was carried out and no more malfunctions