Flicker Emission - IEC 1000-3-3 , EN 61000-3-3 , (EN60555-3)

Comply: IEC 61000-3-3 Ed.1.1 :2002 (incl. Amd.1) - IEC 61000-4-15 Ed.1.0 :1997 (incl. Amd.1)


EMC PARTNER AG, SWITZERLAND
www.emc-partner.com


HARCS Setup File :
D:\HARCS\EXAMPLES\copying-machine.hsu
HARCS Report File :
D:\HARCS\EXAMPLES\copying-machine.hrp

Operator :      		Reto Casanova
Unit :          		Copying Machine : MINOLTA
Serialnumber :  		unknown
Bemerkungen :   		PST is over 1.00



   Full Bar  : Actual Values
   Empty Bar : Maximum Values
   Circles   : Average Values
   Blue : Current , Green : Voltage , Red : Failed



Measurement
                                            Date : 22.08.02 12:02:28 V3.10

Urms = 	229.5V	Freq = 	49.984	Range: 	25 A	
Irms = 	0.708A	Ipk  = 	1.123A	cf   = 	1.586	
P    = 	145.4W	Pap  = 	162.5VA	pf   = 	0.895	

Test - Time :	1 x 10min = 10min	( 100 %)

LIN (Line Impedance Network) :	SLIN 0.24ohm +j0.15ohm N:0.16ohm +j0.10ohm

Limits :	Plt  :	0.00	Pst   :	1.00	
		dmax :	4.00 %	dc    :	3.00 %	
		dtLim:	3.00 %	dt>Lim:	200ms	

Test completed, Result: FAILED

 	Pst	P50s	P10s	P3s	P1s	P0.1s	Fli(m)	dmax	dc	dt>Lim	
 	 	 	 	 	 	 	 	[%]	[%]	[ms]	
1	1.039	0.035	1.174	3.896	5.366	6.686	10.80	1.970	0.640	0.000	


Definitions of Abbreviations
Urms     ***    Actual total Voltage in Volt RMS
Irms     ***    Actual total Current in Ampere RMS
Ipk      ***    Actual Peak value of the Current in Ampere
cf       ***    Actual Crest Factor (Ipk/Irms)
P        ***    Actual Active Power in Watt
Pap      ***    Actual Apparent Power in VA (Urms*Irms)
pf       ***    Actual Power Factor (P/Pap)

Plt             Long term Flicker over all Pst cycles

For every Pst-cycle:

Pst             Short term Flicker
P50s            Flicker level reached during 50% of the test time
P10s            Flicker level reached during 10% of the test time
P3s             Flicker level reached during 3% of the test time
P1s             Flicker level reached during 1% of the test time
P0.1s           Flicker level reached during 0.1% of the test time
Fli(max)        Maximum Flicker level during test time
dmax            Maximum voltage changes between two steady state conditions
dc              Voltage changes between two steady conditions
dt>Lim          Time during the voltage variation go to across
                the defined limit (dtlim)

General :
- The values marked with "***" are actual values which could vary
  during test-time and are taken at the time of protocol printout.


Notes
Flicker measurement on Copying Machine MINOLTA
==============================================

The appliance is tested for Pst at the maximum rate of copying.
The copied original is white blank paper and the copy paper has a 
weight of 80g/m2. Doubble sided copy mode is selected.

The Plt is obtained in stand-by mode in a separate run.

Pst is slightly over 1.00.