EFT Testing requirements per IEC 61000-4-4


Version : 21.03.03 , based on 61000-4-4:1995 /A2:2001

EMC-Partner Generator : TRA2000

 

1. General

Testing take place in climatic specification as follows:
Ambient temperature :               15°C to 35°C
Relative Humidity :                     10% to 75%
Atmospheric Pressure :              86kPa (860 mbar) to 106kPa (1060 mbar)
Other values may be specified in the test specification.

 

 


 

3. Test Levels

3.1. EFT : Power supply 

Level

 

AC power supply,
single phase

AC power supply,
three phase

 

Test Level in kV

Frequency in kHz

TEMA setup

Example

TEMA setup

Example

1

0.5

5

SETUP HTML SETUP HTML

2

1.0

5

SETUP

HTML

SETUP

HTML

3

2.0

5

SETUP

HTML

SETUP

HTML

4

4.0

2.5

SETUP

HTML

SETUP

HTML

 

3.2. EFT : Datalines 

Level

 

 

 

Test Level in kV

Frequency in kHz

TEMA Setup

Example

1

0.25

5

SETUP HTML

2

0.5

5

SETUP

HTML

3

1.0

5

SETUP

HTML

4

2.0

5

SETUP

HTML